Installation

Safety

Qualified Personnel Only

Installation must be carried out by a qualified electrician in accordance with local regulations.

Power Disconnection

Disconnect power before any wiring work. Verify absence of voltage.

All-Pole Disconnection Device Required

As the thermostat is permanently connected, an all-pole disconnection and overcurrent protection device (e.g. a double-pole circuit breaker) must be incorporated in the fixed wiring in accordance with applicable installation rules. This device must simultaneously disconnect all live conductors (line and neutral), with a contact opening distance of at least 3 mm, and must remain accessible after the thermostat is installed.

Circuit Protection

Installation must be carried out on a protected circuit in accordance with applicable installation standards (HD 60364 / NF C 15-100 or equivalent).

Indoor Use Only

Indoor dry locations only (IP20). Do not install in damp or outdoor locations.

Do Not Open

Do not open the housing. No user-serviceable parts inside.

Relay Limitations — Fire Hazard

The thermostat relays provide control signals only. They must not carry the power load of an auxiliary electric heater. The heater must be controlled via an external contactor (power relay) rated for the load. Failure to comply may result in a fire hazard.

Mounting

Install the thermostat on a wall, at a maximum height of 2 m above the floor. The recommended installation height is at person height, at a location representative of the room ambient temperature.

Avoid:

  • Proximity to heat sources (radiator, hot water pipes)
  • Direct sunlight
  • Draughts (doors, windows, ventilation outlets)
  • Dead zones (corners, behind doors)

Steps:

  1. Loosen the bottom screw. Separate the front panel from the rear plate.
  2. Fix the rear plate to the wall.
  3. Proceed with electrical connections (see Terminal Block below and Wiring Configurations).
  4. Reconnect the front panel and tighten the screw.

Note

Do not obstruct the ventilation slots on the housing (required for the sensors).

Terminal Block

Terminal Name Description
N Neutral Neutral conductor
L Line Line conductor
RL1 Relay 1 ON/OFF output 230V~ — Fan high speed (FH)
RL2 Relay 2 ON/OFF output 230V~ — Fan medium speed (FM)
RL3 Relay 3 ON/OFF output 230V~ — Fan low speed (FL) — or heater depending on config.
RL4 Relay 4 ON/OFF output 230V~ — Heating valve (HV)
RL5 Relay 5 ON/OFF output 230V~ — Cooling valve (CV) or heater depending on config.
G 0V Ref. 0V reference for DAC outputs and S1/S2 inputs
DAC1 0-10V output Proportional signal — Heating valve (HV)
DAC2 0-10V output Proportional signal — Cooling valve (CV)
DAC3 0-10V output Proportional signal — Fan
B Reserved Reserved — do not connect
A Reserved Reserved — do not connect
S1 Input 1 External sensor
S2 Input 2 External sensor

Notes

  • Outputs RL1–RL5 are used for ON/OFF control only. Outputs DAC1–DAC3 are used for 0-10V proportional control.
  • The terminal block is divided into two galvanically isolated zones: LV zone (low voltage) 230V~ (N, L, RL1–RL5) and ELV zone (extra-low voltage) 0-10V (G, DAC1–DAC3, B, A, S1, S2).
  • The exact assignment of each output depends on the configuration. Refer to Wiring Configurations.
  • 2-pipe systems: the single valve is connected to the HV output (RL4 or DAC1 depending on configuration).
  • Systems without heater: do not connect anything to the HR output.

Conventions

Abbreviation Meaning
FH Fan high speed
FM Fan medium speed
FL Fan low speed
HV Heating valve
CV Cooling valve
HR Auxiliary electric heater

Wiring Specifications

Parameter Value
Wire gauge — LV 230V~ zone (N, L, RL1–RL5) 1.5 mm²
Wire gauge — ELV 0-10V zone (G, DAC1–DAC3, S1, S2) 0.5 to 0.75 mm²
Max. cable length DAC 0-10V 20 m (shielded cable recommended beyond 10 m)
Max. cable length sensors S1/S2 20 m (shielded cable recommended beyond 10 m)
Wire type Solid or stranded wire with crimped ferrule

Maintenance

  • Do not open the housing. No serviceable parts. No consumables to replace.
  • Clean with a dry or slightly damp cloth. No solvents, abrasives or water jets.
  • Keep ventilation slots clear.
  • The appliance does not release any toxic substances during normal operation.
  • In case of malfunction, contact AGRID or a qualified installer.

Troubleshooting

Symptom Possible cause Action
Screen does not turn on No power supply Check the circuit breaker and voltage at terminals N/L (220-240V~)
Screen turns on then off repeatedly Repeated watchdog restart Disconnect power for 30 s then reconnect. If the problem persists, contact AGRID.
Inconsistent displayed temperature Temperature sensor disturbed Check that ventilation slots are not blocked. Check for nearby heat sources.
Fan or valve does not respond Wrong configuration or incorrect wiring Check the selected configuration (see Wiring). Check wiring. Check the operation of the controlled equipment.
No output is working Unsupported configuration (N/S) or output conflict Select a supported configuration (see Wiring). Outputs are disabled for safety.
No WiFi connection WiFi network unavailable or incorrect credentials Check WiFi 2.4 GHz network availability. Reconfigure directly from the thermostat settings screen or via the AGRID Installer app. The thermostat continues in standalone mode.

| Touchscreen does not respond | Screen in standby or software freeze | Touch the screen to wake it. If no response, disconnect power for 30 s then reconnect. |

Disposal

WEEE Directive

This product must not be disposed of with household waste. In accordance with the WEEE Directive (2012/19/EU), return it to an authorised collection point or to the distributor.